Rosemount 3095 Differential Pressure Transmitter

Type Data source
3095M Product Data Sheet 00813-0100-4716, Rev KA Catalog 2006 – 2007

N.B. no data for U(ps)

Reference Accuracy U(ac)

Type Range Low Turndown High Turndown
Classic 1 for spans less than 15:1
±0.1% of Span
for spans greater than 15:1

2-3 for spans less than 10:1
±0.075% of Span
for spans greater than 10:1

Ultra for Flow 2-3 for spans less than 3:1
±0.05% of Reading
for spans greater than 3:1

Drift (stability) U(d)

Type Range
Classic 1 ±0.2% of URL for 1 year
2-3 ±0.125% of URL for 5 years
Ultra for Flow 2-3 ±0.25% of URL for 10 years

Power supply effect U(ps)

?

Ambient temperature effect U(ac)

Type Range Low Turndown High Turndown
Classic 1 for spans less than 30:1
±(0.2% URL + 0.25% Span)
for spans from 30:1 to 50:1
±(0.24% URL + 0.15% Span)
2-3 for spans less than 30:1
±(0.025% URL + 0.125% Span)
for spans from 30:1 to 100:1
±(0.035% URL – 0.175% Span)
Ultra for Flow 2-3 for spans less than 3:1
±0.13% of Reading
for spans from 3:1 to 100:1

 

 