Honeywell ST3000 Pressure Transmitter
| Type | Data source |
|---|---|
| 100 | Product Data Sheet 34-ST-03-62 Catalog January 2006 |
| 100HT | Product Data Sheet 34-ST-03-70 Catalog January 2006 |
| 900 | Product Data Sheet 34-ST-03-67 Catalog January 2006 |
Reference Accuracy U(ac)
100
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 19L | ![]() |
± 0.075% of calibrated span |
| All other ranges | ![]() |
± 0.075% of calibrated span |
100HT
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 14T | ![]() |
± 0.0875% of calibrated span |
900
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 944 & 94L | ![]() |
± 0.075% of calibrated span |
| All other ranges | ![]() |
± 0.1% of calibrated span |
Drift (stability) U(d)
100
| Range | |
|---|---|
| 140 & 14L | ± 0.015% of URL for 1 year |
| All other ranges | ± 0.03% of URL for 1 year |
100HT
± 0.04% of URL for 1 year
900
| Range | |
|---|---|
| 944 & 94L | ± 0.015% of URL for 1 year |
| All other ranges | ± 0.03% of URL for 1 year |
Power supply effect U(ps)
All Models
Less than ± 0.005% of calibrated span per volt change.
Ambient temperature effect U(ac)
100
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 140 & 14L | ![]() |
± 0.1% of calibrated span |
| All other ranges | ![]() |
± 0.175% of calibrated span |
100HT
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 14T | ![]() |
± 0.1% of calibrated span |
900
Analogue Mode
| Range | Low Turndown | High Turndown |
|---|---|---|
| 944 & 94L | ![]() |
± 0.25% of calibrated span |
| All other ranges | ![]() |
± 0.325% of calibrated span |