PMC71 Endress & Hauser Pressure Transmitter
| Type | Data source |
|---|---|
| PMC71 Standard | Product Data Sheet 2.5M309CW 2012 |
| PMC71 Platinum | Product Data Sheet 2.5M309CW 2012 |
Reference Accuracy U(ac)
Standard
| Range | Sensor | Low Turndown | High Turndown |
|---|---|---|---|
| 100 mbar 250 mbar |
Gauge Gauge & Absolute |
1:1 to 10:1 ± 0.075% |
> 10:1
|
| 100 mbar | Absolute | 1:1 to 5:1 ± 0.075% |
> 5:1 |
| All other ranges | Gauge & Absolute | 1:1 to 10:1 ± 0.05% |
> 10:1
|
Platinum
| Range | Sensor | U(ac) |
|---|---|---|
| 100 mbar & 250 mbar | Gauge & Absolute | ± 0.05% |
| 400 mbar & 1 bar 2 bar & 4 bar 10 bar & 40 bar |
Gauge & Absolute Gauge Gauge & Absolute |
± 0.035% |
| 2 bar & 4 bar | Gauge | ± 0.025% |
Drift (stability) U(d) =
Standard
| Range | Sensor | Stability |
|---|---|---|
| 1 bar | Gauge & Absolute | ± 0.05% of URL for 1 year |
| All other ranges | Gauge | ± 0.2% of URL for 10 years |
| All other ranges | Absolute | ± 0.3% of URL for 10 years |
Platinum
± 0.1% of URL for 1 year
Power supply effect U(ps)
± 0.0006% of calibrated span per volt change.
Ambient temperature effect U(ac)
Standard
| Range | -10°C to 60°C | -20°C to -10°C 60°C to 125°C |
|---|---|---|
| 100, 250 & 400 mbar | ||
| All other ranges | ![]() |
Platinum
Gauge
| Range | -10°C to 60°C | 60°C to 150°C |
|---|---|---|
| 100, 250 & 400 mbar | ||
| All other ranges | ![]() |
Absolute
| Range | -10°C to 60°C | 60°C to 150°C |
|---|---|---|
| 100 mbar | ||
| 250 & 400 mbar | ||
| 40 bar | ![]() |
|
| All other ranges | ![]() |