PMP71 Endress & Hauser Pressure Transmitter
| Type | Data source |
|---|---|
| PMP71 Standard | Product Data Sheet 2.5M309CW 2012 |
| PMP71 Platinum | Product Data Sheet 2.5M309CW 2012 |
Reference Accuracy U(ac)
Standard
| Range | Sensor | Low Turndown | High Turndown |
|---|---|---|---|
| 400 mbar | Gauge & Absolute | 1:1 ± 0.05% |
> 1:1
|
| 1 bar | Gauge & Absolute | 1:1 to 2.5:1 ± 0.05% |
> 2.5:1
|
| 2 bar | Gauge & Absolute | 1:1 to 5:1 ± 0.05% |
> 5:1
|
| 4 bar | Gauge & Absolute | 1:1 to 10:1 ± 0.05% |
> 10:1
|
| 40 bar | Gauge & Absolute | 1:1 to 15:1 ± 0.075% |
> 15:1
|
| 100 bar | Gauge & Absolute | 1:1 to 10:1 ± 0.075% |
> 10:1
|
| 400 bar 700 bar |
Gauge & Absolute Absolute |
1:1 to 5:1 ± 0.15% |
> 5:1
|
Platinum
| Range | Sensor | U(ac) |
|---|---|---|
| 400 mbar & 1 bar 2, 4 & 10 bar |
Gauge & Absolute Absolute |
± 0.035% |
| 2, 4 & 10 bar | Gauge | ± 0.025% |
| 40 bar 100 bar |
Gauge & Absolute Absolute |
± 0.05% |
| 400 & 700 bar | Gauge & Absolute | ± 0.075% |
Drift (stability) U(d)
| for 1 year | for 5 years | for 10 years | |
|---|---|---|---|
| Range | % of URL | ||
| 1 bar | ± 0.02% | ± 0.08% | ± 0.18% |
| 10 bar | ± 0.025% | ± 0.05% | ± 0.075% |
| 40 bar | ± 0.025% | ± 0.075% | ± 0.1% |
| 100 bar | ± 0.05% | ± 0.15% | ± 0.2% |
| 400 bar | ± 0.05% | ± 1.0% | |
Power supply effect U(ps)
± 0.0006% of calibrated span per volt change.
Ambient temperature effect U(ac)
Standard
| Range | -10°C to 60°C | -40°C to -10°C 60°C to 85°C |
|---|---|---|
| 400 mbar |
|
|
| 1, 2, 4, 10 & 40 bar | ![]() |
|
| 100 bar |
|
|
| 400 bar |
|
|
| 700 bar |
|
Platinum
The % of the set span for platinum is 5x the Standard values